Case Study:
TurboWeb High Efficiency filter resulted in reduction of water wash from every 6-8 weeks to once in 1,5 year
Environment:
Coastal environment and located in an industrial area close to a steel furnace. The North Sea and the location in an industrial area equals high humidity, salty and polluted ambience air.
Location:
- NETHERLANDS
Operation:
Gas Turbine Air Inlet
Turbine name:
GE LM2500
Running hours:
Base Load Power plant running 360 days a year
Type of filter:
Cylindrical /Cylindrical sets with TurboWeb HE high efficiency filter media
Amount of filters used:
256 (128 x 2)
Problem:
- The customer wanted to stabilize Dp and reduce water wash.
- Previous fiters needed water wash every 6-8 weeks, had a life cycle of 2 years and initial Dp of 250Pa. Change out DP was 500Pa.
Solution:
Installation of Nordic Air Filtration’s cylindrical filter with TurboWeb HE High Efficiency filter with coalescer.
Results:
- Initial Dp was 250Pa. After 2,5 years, the Dp was only 300Pa.
- Offline water-wash is now conducted every quarter, only due to normal maintenance.
Weeks
after
installation
|
Relative
humidity
[%]
|
Delta P |
Temp.
Celcius
|
Fuel intake
[Nm³/hr]
|
Power
output
[MW]
|
On line
washing
(y/n)
|
Off line
washing
(y/n)
|
1 | 65 | 230 | 4,5 | 6082 | 22 | n | n |
29 | 73 | 290 | 20,3 | 6398 | 21,8 | n | y* |
63 | 64,9 | 280 | 10,6 | 6340 | 21,9 | n | n |
115 | 64,9 | 300 | 10,6 | 6340 | 21,9 | n | n |
*Wash due to turbine changeout - no visible contamination on 3 first rows of blades